Electrical question-240V breaker. - Charles Bishop - 2009-04-17 19:39:00

I wanted to shut off an electric wall heater so I went to the breaker box
looking for a doubled 20A breaker since the heater is 3000 watts/240V.
Turned off all I could find, but the heater still works. [Long story about
testing this and that breaker omitted] Turns out the heater is controlled
by two 20 amp breakers, but they are not tied together. One is on the RH
side of the breaker box at position #1. The second is at position #6.
(both are split breakers, part of a pair that occupies one space on the
breaker panel)

1.  Should these two breakers be ganged together?

2.  If one trips this effectively shuts down the heater doesn't it? That
is, the heater will no longer provide heat.

3.  Is there still a problem since the 2nd breaker hasn't tripped? I mean
other than a possible danger to someone futzing around in the heater's
innards.

-- 
charles

Re: Electrical question-240V breaker. - Nate Nagel - 2009-04-17 19:50:00

Charles Bishop wrote:
> I wanted to shut off an electric wall heater so I went to the breaker box
> looking for a doubled 20A breaker since the heater is 3000 watts/240V.
> Turned off all I could find, but the heater still works. [Long story about
> testing this and that breaker omitted] Turns out the heater is controlled
> by two 20 amp breakers, but they are not tied together. One is on the RH
> side of the breaker box at position #1. The second is at position #6.
> (both are split breakers, part of a pair that occupies one space on the
> breaker panel)
> 
> 1.  Should these two breakers be ganged together?
> 
> 2.  If one trips this effectively shuts down the heater doesn't it? That
> is, the heater will no longer provide heat.
> 
> 3.  Is there still a problem since the 2nd breaker hasn't tripped? I mean
> other than a possible danger to someone futzing around in the heater's
> innards.
> 

It's not really a *problem* per se (functionally that is) but it 
certainly is a hazard for a maintenance person and highly not to code. 
I suggest that it's time to rearrange your breaker panel so that the 
water heater can be fed by a proper 240V breaker, or worst case, two 
double breakers next to each other with the two handles feeding the 
heater tied together.

nate

-- 
replace "roosters" with "cox" to reply.
http://members.cox.net/njnagel

Re: Electrical question-240V breaker. - RBM - 2009-04-17 21:21:00

"Charles Bishop" <c...@earthlink.net> wrote in message 
news:c...@dialup-4.246.238.120.dial1.sanjose1.level3.net...
>I wanted to shut off an electric wall heater so I went to the breaker box
> looking for a doubled 20A breaker since the heater is 3000 watts/240V.
> Turned off all I could find, but the heater still works. [Long story about
> testing this and that breaker omitted] Turns out the heater is controlled
> by two 20 amp breakers, but they are not tied together. One is on the RH
> side of the breaker box at position #1. The second is at position #6.
> (both are split breakers, part of a pair that occupies one space on the
> breaker panel)
>
> 1.  Should these two breakers be ganged together?
>
> 2.  If one trips this effectively shuts down the heater doesn't it? That
> is, the heater will no longer provide heat.
>
> 3.  Is there still a problem since the 2nd breaker hasn't tripped? I mean
> other than a possible danger to someone futzing around in the heater's
> innards.
>
> -- 
> charles

There are a number of scenarios that could be potentially dangerous if both 
legs didn't trip simultaneously. Depending upon the make and model of the 
panel, there are half size double pole breakers, as well as dual double pole 
breakers (quads) to correct your situation 



Re: Electrical question-240V breaker. - sym - 2009-04-17 22:20:00

On Apr 17, 7:39=A0pm, c...@earthlink.net (Charles Bishop) wrote:
> I wanted to shut off an electric wall heater so I went to the breaker box
> looking for a doubled 20A breaker since the heater is 3000 watts/240V.
> Turned off all I could find, but the heater still works. [Long story abou=
t
> testing this and that breaker omitted] Turns out the heater is controlled
> by two 20 amp breakers, but they are not tied together. One is on the RH
> side of the breaker box at position #1. The second is at position #6.
> (both are split breakers, part of a pair that occupies one space on the
> breaker panel)
>
> 1. =A0Should these two breakers be ganged together?
>
> 2. =A0If one trips this effectively shuts down the heater doesn't it? Tha=
t
> is, the heater will no longer provide heat.
>
> 3. =A0Is there still a problem since the 2nd breaker hasn't tripped? I me=
an
> other than a possible danger to someone futzing around in the heater's
> innards.
>
> --
> charles

 yes they should be tied together ,the heater will no longer work
missing 120v,should trip if overloaded or shorts. how many space/cir
panel do you have  and are all your breakers tandems or 240v

Re: Electrical question-240V breaker. - John Grabowski - 2009-04-18 07:23:00

"Charles Bishop" <c...@earthlink.net> wrote in message 
news:c...@dialup-4.246.238.120.dial1.sanjose1.level3.net...
>I wanted to shut off an electric wall heater so I went to the breaker box
> looking for a doubled 20A breaker since the heater is 3000 watts/240V.
> Turned off all I could find, but the heater still works. [Long story about
> testing this and that breaker omitted] Turns out the heater is controlled
> by two 20 amp breakers, but they are not tied together. One is on the RH
> side of the breaker box at position #1. The second is at position #6.
> (both are split breakers, part of a pair that occupies one space on the
> breaker panel)
>
> 1.  Should these two breakers be ganged together?


*Absolutely.   Clearly a code violation and a potential safety hazard.



> 2.  If one trips this effectively shuts down the heater doesn't it? That
> is, the heater will no longer provide heat.


*That is correct.




> 3.  Is there still a problem since the 2nd breaker hasn't tripped? I mean
> other than a possible danger to someone futzing around in the heater's 
> innards.



*Possibly. If an element happened to be shorted to ground, current would 
flow and the element would put out some heat where it is not supposed to. 
Not a likely scenario, but a possible one. 


Re: Electrical question-240V breaker. - Stormin Mormon - 2009-04-18 21:33:00

1.  Should these two breakers be ganged together?

Yes. I'm reasonably sure the electrical code requires it. In 
any case, it's the safe thing to do.

2.  If one trips this effectively shuts down the heater 
doesn't it? That
is, the heater will no longer provide heat.

Yes, tripping one breaker will stop the heat from comign 
out.

3.  Is there still a problem since the 2nd breaker hasn't 
tripped? I mean
other than a possible danger to someone futzing around in 
the heater's
innards.

The wires are still electrically charged, so this is a 
safety problem for someone futzing around in the heater's 
innards, trying to figure out why it's not heating. Double 
pole breakers aren't that expensive. Since you're asking 
these questions, I'm guessing you don't feel comfortable 
replacing your own breaker. Call a friend who is, or an 
electrician.